How to set up and debug the Fisher DVC6200 locator using the 475 hand controller with illustrations and explanations.
On-site, our factory's instrumentation workers often use the 475 handheld communicator to set up and debug the Fisher DVC6200 positioner. Since we usually need to perform initial guiding setup and debugging after purchasing and using the Fisher DVC6200 positioner, not all users can correctly set it up and debug it. Today, the technical editor from Shaanxi Huibo Electromechanical will explain how to set up and debug the Fisher DVC6200 positioner using the 475 handheld communicator with illustrations.
Release time:
2022-02-16
Source:
On-site, our factory's instrument workers often use the 475 handheld communicator to set up and debug the Fisher DVC6200 positioner. Since we usually need to perform initial guided setup and debugging after purchasing and using the Fisher DVC6200 positioner, not all users can set it up correctly. Today, the technical editor from Shaanxi Huibo Electromechanical will explain how to set up and debug the Fisher DVC6200 positioner using the 475 handheld communicator with images and text.
The specific steps for initial guided setup and debugging are as follows:

Enter the interface and select HART

SelectOnline

If there is an alarm signal, selectYES

OnlineFrom the drop-down menu, selectConfigure(Configuration)

SelectGuided Setup(Guided Setup) menu

SelectDevice Setup

Select from the warning menuOut of Service

Pressure unit selection can be arbitrary, selectPsi

Amplifier type, selectA or CFor single-acting and double-acting amplifiers,BFor reverse-acting positioners.

SelectTravel ControlTravel Control

Select actuator manufacturerFisher(If it is a domestic actuator, select according to specific parameters corresponding to the actuator)Fisher执行机构来选)

Select the actuator model based on the actuator nameplate.

Select the actuator size model also based on the actuator nameplate input.

For valve air open and air close, select based on conditions.

Start driving the valve, set the travel sensor action, selectYES

The positioner automatically captures the travel sensor action. Wait for the following interface to pop up.

Based on the attachments installed on-site for the actuator, select whether it includes a flow amplifier and quick exhaust valve, selectYes, selectno.

Send device setup data to the instrument, pressEnter

Wait for sending, after sending is complete, the following interface will appear.

Select to use factory default settings.YES

Send factory default data, wait for completion, and the following interface will appear.

Device setup is complete, selectOK

To complete the valve setup, it is necessary to run the valve automatic travel calibration, selectOK

SelectYes

During valve automatic calibration, capture high and low drive points respectively.

Adjust output deviation.

Waiting during automatic calibration.

Valve calibration is complete, pointOK

SelectOK

After calibration is complete, restore toIn Servicestatus. The valve automatic calibration steps are complete.
Key words:
Rosemount handheld device, 475 handheld device, setup and debugging, Fisher DVC6200 positioner
Related News
Temperature measurement is an important and fundamental feature of most industrial process control. So how do you choose the correct temperature transmitter for reliable temperature measurement and detection?
DVC2000 vs DVC6200: What’s the Difference Between Fisher FIELDVUE Digital Valve Positioners?
Both Fisher DVC2000 Digital Valve Positioner and Fisher DVC6200 Digital Valve Positioner are perhaps two-star products in Emerson's Fisher FIELDVUE product range.
Understanding the Working Process of Fisher FIELDVUE DVC2000 Digital Valve Controller
Fisher FIELDVUE DVC2000 is a digital valve controller. It is fed with a 4-20mA control signal and then the commands are processed by means of a microcontroller.
Differential pressure transmitters are a critical part of flow measurement systems. If you use the wrong transmitter, your measurements will be inaccurate, your processes will not run smoothly, and you may even shut down.
Rosemount 2088 Pressure Transmitter or Rosemount 3051 Transmitter-Which One Is Right For Me?
The selection of pressure transmitters for industrial processes often puts engineers in a dilemma between the Rosemount 2088 and the Rosemount 3051.
How Does Yokogawa YTA710 Dual Input Temperature Transmitter Work? YTA710 Working Principle Explained
Yokogawa YTA710 Smart Temperature Transmitter is a best-selling smart temperature transmitter produced by Japan Yokogawa.
Related Products